5. Insulation Work
5.1 Insulation material and thickness
5.1.1. Insulation material
Insulation material should adopt the material which is able to endure the pipe’s temperature: no less than
70 in the high℃ -pressure side, no less than 120 in the low℃ -pressure side(For the cooling type machine, no
requirements at the low-pressure side.)
u Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above 120)℃
Cooling only type----Polyethylene foam (withstand above 100) ℃
5.1.2. Thickness choice for insulation material
Insulation material thickness is as follows:
Pipe diameter (mm) Adiabatic material thickness
Refrigerant pipe
Φ6.4—Φ25.4 10mm
Φ28.6—Φ38.1 15mm
Drainage pipe
Inner diameterΦ20—Φ32 6mm
5.2 Refrigerant pipe insulation
5.2.1. Work Procedure
Before laying the pipes, the non① -jointing parts and non-connection parts should be heat insulated.
When the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat ②
insulated
5.2.2. Insulation for non-jointing parts and non-connection parts
wrong right
Gas pipe and liquid pipe should
not be put together to insulate
Insulate the gas pipe
(cooling only)
Insulate the gas pipe and
liquid pipe